Star and delta
In a star connection the line current equals the phase current and the line voltage is √3 times the phase voltage: Ul = √3·Uph. In a delta connection the phase voltage equals the line voltage and a line current is the difference of the adjacent phase currents; for a balanced load Il = √3·Iph.
Neutral shift
Without a neutral wire and with an unbalanced load the load neutral potential shifts: U(N'n) = (Ya·Ea + Yb·Eb + Yc·Ec) / (Ya + Yb + Yc), where Y = 1/Z. The phase voltages are no longer equal: some phases are overloaded, others underloaded. A low-impedance neutral wire fixes the neutral but carries In = Ia + Ib + Ic.
Open and short circuit
An open phase in a star without neutral leaves the other two in series across the line voltage. A shorted phase in a star without neutral raises the voltage on the other phases to the line voltage. In a delta an open branch does not change the other branch currents.
Power
For each phase S = U·I* = P + jQ, the total is the sum over phases. For a balanced load P = √3·Ul·Il·cos φ. For an unbalanced load the overall cos φ = P/S is only a figure of merit: it equals the cosine of none of the phase angles.
Topographic diagram
Every circuit point maps to a point on the complex plane, and the potential difference between two points is the vector between them. The diagram shows the line voltages (sides of triangle ABC), load phase voltages (from N' to the vertices) and the neutral shift (segment n–N').